  1.                          SECTION 06072
  2.  
  3.                 FIRE-RETARDANT TREATMENT OF WOOD
  4. NOTE ** This section is based on products manufactured by
  5.         Hoover Treated Wood Products, Inc., at the
  6.         following address:
  7. NOTE **      P.O. Box 746
  8. NOTE **      Thomson, GA  30824.
  9. NOTE **      Telephone:  800-832-9663.
  10. NOTE **      FAX:  706-595-1326.
  11. NOTE **
  12. NOTE ** "Pyro-Guard" is a UL listed third-generation Type
  13.         "A" (low-hygroscopic) treatment for lumber and
  14.         plywood used in interior structural and non-
  15.         structural applications, with strength ratings for
  16.         use at elevated temperatures that have been
  17.         reviewed by the National Evaluation Service, Inc.
  18. NOTE **
  19. NOTE ** SECTION 06072 - FIRE-RETARDANT TREATMENT OF WOOD,
  20.         Copyright 1996, The Architect's Catalog, Inc.
  21. NOTE ** This specification section is for treatment only.
  22.         Grades and species of plywood and lumber to be
  23.         treated must be specified separately.  See Related
  24.         Sections article below.
  25.  
  26. PART 1 - GENERAL
  27.  
  28. 1.1 SECTION INCLUDES
  29. NOTE ** Delete items below not required for project.
  30.  
  31.     A.  Fire-retardant treatment for the following:
  32.         1.  Wood framing.
  33.         2.  Decking.
  34.         3.  Sheathing.
  35.         4.  Blocking.
  36.         5.  Miscellaneous rough carpentry.
  37.         6.  Wood siding.
  38.         7.  Wood trim and moldings.
  39.         8.  Wood frames for doors, windows, and glazed lights.
  40.         9.  _________.
  41.  
  42. 1.2 RELATED SECTIONS
  43. NOTE ** Delete any sections below not relevant to this
  44.         project;  add others as required.
  45.  
  46.     A.  Section 06075 - Preservative Treatment of Wood.
  47.  
  48.     B.  Section 06100 - Rough Carpentry.
  49.  
  50.     C.  Section 06110 - Wood Framing.
  51.  
  52.     D.  Section 06112 - Wood Framing and Sheathing.
  53.  
  54.     E.  Section 06114 - Wood Blocking and Curbing.
  55.  
  56.     F.  Section 06130 - Heavy Timber Construction.
  57.  
  58.     G.  Section 06150 - Wood Decking.
  59.  
  60.     H.  Section 06170 - Prefabricated Structural Wood.
  61.  
  62.     I.  Section 06200 - Finish Carpentry.
  63.  
  64.     J.  Section 06400 - Architectural Woodwork.
  65.  
  66. 1.3 REFERENCES
  67. NOTE ** Delete references from the list below that are not
  68.         actually required by the text of the edited
  69.         section.
  70.  
  71.     A.  ASTM E 84 - Standard Test Method for Surface Burning
  72.         Characteristics of Building Materials.
  73.  
  74.     B.  MIL-L-1914O - Lumber and Plywood, Fire-Retardant Treated.
  75.  
  76.     C.  NFPA 255 - Standard Method of Test of Surface Burning
  77.         Characteristics of Building Materials; National Fire
  78.         Protection Association.
  79.  
  80.     D.  UL 723 - Standard Test Method for Surface Burning
  81.         Characteristics of Building Materials;  Underwriters
  82.         Laboratories, Inc.
  83.  
  84. 1.4 SUBMITTALS
  85.  
  86.     A.  Submit under provisions of Section 01300.
  87.  
  88.     B.  Product Data:
  89.         1.  National Evaluation Report indicating limitation of
  90.             use, high temperature strength testing, and flame
  91.             spread, corrosion, and hygroscopic properties.
  92.         2.  Manufacturer's product specifications, storage
  93.             instructions, and installation instructions.
  94.  
  95.     C.  Samples:  Supply samples for finishing where finish
  96.         samples are required by other sections of the
  97.         specifications.
  98.  
  99.     D.  Certificates:  Submit wood treater's specifications
  100.         showing compliance with referenced standards.
  101.  
  102. 1.5 DELIVERY, STORAGE, AND HANDLING
  103.  
  104.     A.  Store products indoors and protect from moisture,
  105.         construction traffic, and damage.
  106.  
  107. PART 2 - PRODUCTS
  108.  
  109. 2.1 MANUFACTURER
  110.  
  111.     A.  Provide fire-retardant wood treatment by or licensed by
  112.         Hoover Treated Wood Products, Inc., P.O. Box 746,
  113.         Thomson, GA  30824.  Telephone 800-832-9663.  FAX 706-595-
  114.         1326.
  115.  
  116.     B.  Requests for substitutions will be considered in
  117.         accordance with provisions of Section 01600.
  118. NOTE ** Delete paragraph above or below;  coordinate with
  119.         Division 1 requirements.
  120.  
  121.     C.  Substitutions:  Not permitted.
  122.  
  123. 2.2 MATERIALS
  124.  
  125.     A.  "Pyro-Guard" third generation fire-retardant treated
  126.         wood, complying with MIL-L-19140.
  127.  
  128.     B.  Fire Retardancy:
  129.         1.  Flame spread, when tested in accordance with ASTM E
  130.             84, NFPA 255, or UL 723:  Not more than 25.
  131.         2.  Smoke toxicity: No more than that of untreated wood.
  132.         3.  Each piece shall bear the UL Classification Mark
  133.             certifying flame spread rating.
  134.         4.  When test is extended for 20 additional minutes (30
  135.             minutes total), the flame front shall not extend more
  136.             than 10.5 feet from the center line of the burner and
  137.             there shall be no evidence of significant progressive
  138.             combustion.
  139.         5.  Treatment formulation shall contain no halogens,
  140.             sulfates, chlorides, ammonium phosphate, oils, or
  141.             solvents.
  142.  
  143.     C.  Reviewed by the National Evaluation Service, Inc. for
  144.         structural use at elevated temperatures.
  145.  
  146.     D.  Production and kiln drying after treatment monitored by
  147.         Timber Products Inspection, Inc.
  148.  
  149.     E.  Kiln dry lumber to 19 percent or less moisture content
  150.         after treatment.
  151.  
  152.     F.  Kiln dry plywood to 15 percent or less moisture content
  153.         after treatment.
  154.  
  155. 2.3 FABRICATION
  156.  
  157.     A.  Milling:  Lumber shall be ripped or run to pattern, as
  158.         required, prior to treatment.
  159.  
  160. PART 3 - EXECUTION
  161.  
  162. 3.1 EXAMINATION
  163.  
  164.     A.  Discard pieces with defects which might impair quality or
  165.         work.
  166.  
  167. 3.2 FIELD CUTTING
  168.  
  169.     A.  Lumber:  Do not rip or mill lumber after fire-retardant
  170.         treatment; end cuts, drilling of holes, and joining cuts
  171.         are permitted.
  172.  
  173.     B.  Plywood:  Fire-retardant-treated plywood can be cut in
  174.         any direction.
  175.  
  176. 3.3 ADJUST AND CLEAN
  177.  
  178.     A.  Remove scraps and debris from site, and leave in a broom-
  179.         clean condition.
  180.  
  181.                          END OF SECTION